Multi-split outdoor unit
Inventor U6RSL(2)-18
Multi-split outdoor unit · 5.28 kW (18 000 BTU/h) · 1–2 indoor unit · R-32
- Capacity18 000 BTU
Current price, stock and delivery terms are on shop.inventor.ge. Advice: 599 307 417 · luka@inventor.ge
An outdoor unit from Inventor’s updated multi-split range that connects up to 2 indoor units. It works with any type of indoor unit, so one outdoor unit can create the right climate in every room of a building.
Each indoor unit has its own electronic expansion valve for precise control and efficient operation, and the Golden Fin coating protects the condenser from corrosion.
Key features
- Electronic expansion valve on every circuitEach indoor unit has its own valve — precise control and efficient operation
- Golden Fin coatingA gold anti-corrosion layer on the condenser protects the unit from the weather; suits coastal and humid areas
- A+++ energy class in heatingSCOP 5.1 in the warmer climate zone (EN 14825)
- Heating and cooling even at −15 °CEfficient operation at low outdoor temperatures
- All DC InverterDC inverter compressor and fans; up to 25 compressor frequency steps (F1–F25) for smooth operation
- Quiet operationOptimised airflow and Silent mode for even lower noise
- Auto restart and self-diagnosisAfter a power cut the unit restarts with its previous settings; on a fault it stops and shows an error code
Specifications
| Cooling capacity | 5.28 (2.23–5.57) kW · 18 000 (7 600–19 000) BTU/h |
|---|---|
| Heating capacity | 5.57 (2.34–5.63) kW · 19 000 (7 980–19 200) BTU/h |
| Seasonal efficiency — cooling | Pdesign 5.3 kW · SEER 6.1 · A++ |
| Seasonal efficiency — heating, average climate | Pdesign 4.3 kW · SCOP 4.0 · A+ |
| Seasonal efficiency — heating, warmer climate | Pdesign 5.0 kW · SCOP 5.1 · A+++ |
| Voltage / frequency / phase | 220–240 V / 50 Hz / single-phase |
| Connectable indoor units (min.–max.) | 1–2 |
| Sound pressure level | 56 dB(A) |
| Sound power level | 65 dB(A) |
| Compressor | Rotary, DC Inverter |
| Refrigerant | R-32 × 1250 g |
| Liquid / gas pipe diameter | 2 × (1/4″ / 3/8″) |
| Circuit breaker | 1 × 16 A |
| Max. total piping length | 40 m |
| Max. piping length per indoor unit | 25 m |
| Max. height difference, indoor to outdoor | 15 m |
| Max. height difference between indoor units | 10 m |
| Operating range (outdoor air), cooling | −15 … +50 °C |
| Operating range (outdoor air), heating | −15 … +24 °C |
| Dimensions (W × D × H) | 805 × 330 × 554 mm |
| Net weight | 35 kg |
Seasonal efficiency determined according to EN 14825.